Site icon T4Tutorials.com

Voltage Sag, Swell, and Flicker — MCQs – EE

1. A voltage sag (dip) is defined as:

(A) A short-duration reduction in RMS voltage


(B) A permanent voltage reduction


(C) An increase in voltage magnitude


(D) A zero-voltage condition lasting hours



2. A voltage swell is:

(A) A short-duration increase in RMS voltage


(B) A long-term decrease in voltage


(C) A sustained overcurrent


(D) A frequency deviation



3. The typical duration of voltage sags and swells is:

(A) 0.5 cycles to 1 minute


(B) Several hours


(C) Microseconds only


(D) More than 1 day



4. The main causes of voltage sags are:

(A) Short circuits and starting of large motors


(B) Overvoltage


(C) Capacitor switching


(D) Lightning strikes only



5. Voltage swells are usually caused by:

(A) Sudden load reduction or switching off large loads


(B) Motor starting


(C) Ground faults


(D) Short circuits



6. The magnitude of a voltage sag is typically:

(A) 10% to 90% of nominal voltage


(B) 100% of nominal voltage


(C) Zero volts only


(D) Greater than 200% of nominal voltage



7. The magnitude of a voltage swell is usually:

(A) 110% to 180% of nominal voltage


(B) 50% to 90%


(C) Zero volts


(D) More than 300%



8. Flicker is caused by:

(A) Rapid and repetitive voltage fluctuations


(B) Harmonics only


(C) Sustained overvoltage


(D) Frequency deviations



9. Voltage flicker mainly affects:

(A) Lighting systems


(B) Transformers


(C) Capacitors


(D) Heaters



10. The standard limits for voltage sags and swells are defined by:

(A) IEC 61000-2-2 and IEEE 1159


(B) IEEE 519 only


(C) IEC 60034


(D) NEMA MG1



11. The duration of flicker that causes noticeable light intensity variations is typically:

(A) 0.5 to 30 Hz


(B) 50–60 Hz


(C) Less than 0.1 Hz


(D) More than 100 Hz



12. The short-term flicker severity is measured by:

(A) Plt


(B) THD


(C) RMS voltage


(D) Power factor



13. The long-term flicker severity is measured by:

(A) Pst


(B) Plt


(C) THD


(D) RMS current



14. The main sources of voltage flicker include:

(A) Arc furnaces, large motor starting, welding machines


(B) Lighting loads only


(C) Transformers


(D) Resistive heaters only



15. Voltage sag duration is classified as:

3 min)’)”> (A) Momentary (<0.5 s), Temporary (0.5 s–3 min), Sustained (>3 min)


3 min)’)”> (B) Microseconds only


3 min)’)”> (C) Hours only


3 min)’)”> (D) Days



16. A swell lasting more than 3 minutes is considered:

(A) Sustained overvoltage


(B) Momentary swell


(C) Voltage flicker


(D) Sag



17. Voltage sag mitigation can be achieved using:

(A) Uninterruptible Power Supplies (UPS) and voltage regulators


(B) Harmonic filters only


(C) Transformers only


(D) Reactors only



18. Voltage swell mitigation includes:

(A) Tap-changing transformers and surge protection


(B) Reducing load


(C) Capacitor switching


(D) Induction motors



19. Flicker reduction methods include:

(A) Load balancing, static VAR compensators, and smoothing reactors


(B) Increasing voltage


(C) Removing transformers


(D) Reducing frequency



20. Momentary voltage dips are mostly caused by:

(A) Faults on the transmission system


(B) Capacitor switching


(C) Reactive power compensation


(D) Resistive loads



21. Voltage sags can cause:

(A) Tripping of motors and sensitive electronic equipment


(B) Reduced heating losses


(C) Reduced harmonic currents


(D) Improved insulation life



22. Voltage swell can cause:

(A) Insulation stress and equipment damage


(B) Reduced transformer losses


(C) Motor startup improvement


(D) Harmonic reduction



23. Flicker severity is evaluated by:

(A) Measuring voltage fluctuations and perceptible light variations


(B) RMS voltage only


(C) Current harmonics


(D) System frequency



24. The IEEE Standard 1453 deals with:

(A) Measurement and assessment of voltage flicker


(B) Harmonic limits


(C) Surge protection


(D) Power factor correction



25. Voltage sag and swell monitoring uses:

(A) RMS voltage monitoring instruments


(B) Power factor meters only


(C) Frequency counters


(D) Thermal sensors



26. Dynamic voltage restorers (DVRs) are used to:

(A) Mitigate voltage sags and swells in real-time


(B) Correct frequency deviations only


(C) Reduce harmonic currents


(D) Increase load power factor



27. The main impact of voltage flicker is:

(A) Visible light intensity fluctuations causing annoyance


(B) Motor overheating


(C) Capacitor failure


(D) Reduced THD



28. Power electronic converters can cause:

(A) Both voltage sags and flicker


(B) Only overvoltage


(C) Frequency drift only


(D) Reduced load current



29. Industrial arc furnaces are a major source of:

(A) Voltage flicker


(B) Steady voltage


(C) Reduced harmonic distortion


(D) Overvoltage protection



30. The main goal of addressing voltage sags, swells, and flicker is to:

(A) Ensure reliable, stable, and disturbance-free operation of electrical equipment


(B) Reduce system frequency only


(C) Increase load current


(D) Improve reactive power only



Exit mobile version